Effects of Degraded Optical Fiber Sheaths on Thermal Aging Characteristics of Transformer Oil

被引:17
作者
Liu, Yunpeng [1 ]
Jiang, Shuo [1 ]
Fan, Xiaozhou [1 ]
Tian, Yuan [1 ]
机构
[1] North China Elect Power Univ, State Key Lab New Energy & Elect Power Syst, 619 North Yonghua St, Baoding 071003, Peoples R China
来源
APPLIED SCIENCES-BASEL | 2018年 / 8卷 / 08期
基金
中国国家自然科学基金;
关键词
transformer; optical fiber; copolymer; thermal aging properties; INSULATION; PAPER;
D O I
10.3390/app8081401
中图分类号
O6 [化学];
学科分类号
0703 ;
摘要
With the development of fiber optic sensing technology, optical fiber sensors have been widely used in online monitoring of power transformers. To investigate the influence of aging fiber sheaths on transformer oil, two kinds of special optical fibers with thermoplastic polyester elastomer (TPEE) and poly tetra fluoroethylene (PTFE) as sheaths underwent thermally accelerated aging in transformer oil at 130 degrees C. The volume resistivity, dielectric dissipation factor (DDF), and breakdown voltage of the oil were measured to indicate insulation strength. The water content and acid value of the oil were measured and fitted to predict the aging tends. The thermal aging characteristics of the oil were quantitatively compared and results showed two kinds of optical fibers could exacerbate all the physical and chemical parameters of oil, and the TPEE sheath had a more significant impact on the oil. The reasons contributing to such phenomenon were analyzed using Fourier transform infrared spectroscopy (FTIR) and scanning electron microscopy (SEM). Both TPEE and PTFE were depolymerized in high-temperature transformer oils, producing water and small molecule hydrocarbon groups. The accumulation of small hydrocarbon groups promoted positive feedback of pyrolysis in the oil. The free hydrogen produced by oil pyrolysis increased the acidity of the oil, which in turn increased the solubility of the water produced by sheath depolymerization. The chain depolymerization of TPEE was more severe than that of PTFE, further exacerbating the deterioration of TPEE-containing oil.
引用
收藏
页数:12
相关论文
共 30 条
[1]   Causes of transformer failures and diagnostic methods - A review [J].
Christina, A. J. ;
Salam, M. A. ;
Rahman, Q. M. ;
Wen, Fushuan ;
Ang, S. P. ;
Voon, William .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2018, 82 :1442-1456
[2]   Quasi-Distributed Optical Fiber Transducer for Simultaneous Temperature and Vibration Sensing in High-Power Generators [J].
Dreyer, Uilian Jose ;
Mezzadri, Felipe ;
Dutra, Guilherme ;
da Silva, Thiago ;
Bavastri, Carlos Alberto ;
da Silva, Erlon Vagner ;
Martelli, Cicero ;
Cardozo da Silva, Jean Carlos .
IEEE SENSORS JOURNAL, 2018, 18 (04) :1547-1554
[3]  
[高树国 Gao Shuguo], 2017, [高电压技术, High Voltage Engineering], V43, P2599
[4]   Mechanical properties of thermoplastic polyester elastomer controlled by blending with poly(butylene terephthalate) [J].
Huang, Jing ;
Wang, Jun ;
Qiu, Yaxin ;
Wu, Defeng .
POLYMER TESTING, 2016, 55 :152-159
[5]   Identification and Localization of Partial Discharge in Transformer Insulation Adopting Cross Recurrence Plot Analysis of Acoustic Signals Detected using Fiber Bragg Gratings [J].
Kanakambaran, Srijith ;
Sarathi, R. ;
Srinivasan, Balaji .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (03) :1773-1780
[6]   EFFECT OF ANTIOXIDANTS AND METAL DEACTIVATOR ON THE OXIDATION OF TRANSFORMER OIL [J].
KRISHNAMOORTHY, PR ;
VIJAYAKUMARI, S ;
SANKARALINGAM, S .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1992, 27 (02) :271-277
[7]  
Liao Rui-jin, 2010, High Voltage Engineering, V36, P1090
[8]  
Liao Rui-jin, 2008, Proceedings of the CSEE, V28, P142
[9]   Quantitative Analysis of Ageing Condition of Oil-paper Insulation by Frequency Domain Spectroscopy [J].
Liao, Ruijin ;
Hao, Jian ;
Chen, G. ;
Yang, Lijun .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2012, 19 (03) :821-830
[10]  
Lingvay I, 2017, REV CHIM-BUCHAREST, V68, P2551