Evaluation of position of a fault current limiter with regard to the circuit breaker

被引:8
作者
Alcida, Anthony Frantz [1 ]
Saint Paul, Moreau, Jr. [1 ]
Calixte, Evenson [1 ]
机构
[1] Quisqueya Univ, Dept Elect Engn, Port Au Prince, Haiti
来源
2006 38TH ANNUAL NORTH AMERICAN POWER SYMPOSIUM, NAPS-2006 PROCEEDINGS | 2006年
关键词
rate of rise of recovery voltage; location of FCL; circuit breaker; source-side voltage of FCL;
D O I
10.1109/NAPS.2006.359614
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Calculations were performed to examine the optimum location of a fault current limiter (FCL) with regard to the circuit breaker. The series-connected FCL was assumed to be associated with the circuit breaker in two positions: upstream and downstream from the circuit breaker. In both cases, the characteristics of the transient recovery voltage (TRV) appearing across the circuit breaker with FCL were studied under several fault locations. For both locations of FCL, the presence of the FCL reduces the severity of the circuit breaker duty. Whereas the difference in location of the FCL leads to no variation in the TRV characteristics and the fault current, locating the FCL downstream proved to lessen the voltage at the source-side terminal of the FCL, compared with the FCL located upstream from the circuit breaker. In other words, a gain in the device safety can be obtained by locating the FCL downstream from the circuit breaker.
引用
收藏
页码:475 / +
页数:3
相关论文
共 29 条
[1]   Theoretical expression of rate of rise of recovery voltage across a circuit breaker connected with fault current limiter [J].
Calixte, E ;
Yokomizu, Y ;
Shimizu, H ;
Matsumura, T .
ELECTRIC POWER SYSTEMS RESEARCH, 2005, 75 (01) :1-8
[2]   Reduction of rating required for circuit breakers by employing series-connected fault current limiters [J].
Calixte, E ;
Yokomizu, Y ;
Shimizu, H ;
Matsumura, T ;
Fujita, H .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2004, 151 (01) :36-42
[3]  
CALIXTE E, 2004, P 36 ANN N AM POW S, P456
[4]  
CALIXTE E, 2004, IEEJ T PE, V124, P843
[5]  
CALIXTE E, 2003, P 35 ANN N AM POW S, P545
[6]  
CALIXTE E, 2005, THEORETICAL EVALUATI, P317
[7]  
CALIXTE E, 2004, INT J POWER ENERGY S, P24
[8]   Integration of fault current limiters on power systems for voltage quality improvement [J].
Chang, CS ;
Loh, PC .
ELECTRIC POWER SYSTEMS RESEARCH, 2001, 57 (02) :83-92
[9]   FIELD-TEST RESULTS FOR A MULTISHOT 12.47 KV FAULT CURRENT LIMITER [J].
ENGELMAN, N ;
SCHREURS, E ;
DRUGGE, B .
IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (03) :1081-1087
[10]  
FLURSCHEIM CH, 1982, IEE POWER ENG SERIES, V1, P64