Achieving better energy-efficient air conditioning - A review of technologies and strategies

被引:706
作者
Chua, K. J. [1 ]
Chou, S. K. [1 ]
Yang, W. M. [1 ]
Yan, J. [2 ,3 ]
机构
[1] Natl Univ Singapore, Dept Mech Engn, Singapore 117576, Singapore
[2] Royal Inst Technol, Stockholm, Sweden
[3] Malardalen Univ, Sch Sustainable Dev Soc & Technol, Gasmyrevreten, Vasteras, Sweden
关键词
Air conditioning; Energy efficiency; Novel cooling technologies; Cogeneration/trigeneration; Waste heat recovery; ADSORPTION COOLING SYSTEM; HEAT-PUMP SYSTEM; CLIMATE-CHANGE; PERFORMANCE ANALYSIS; THERMAL COMFORT; CHILLER; OPTIMIZATION; COMPRESSOR; BUILDINGS; DESIGN;
D O I
10.1016/j.apenergy.2012.10.037
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Air conditioning is essential for maintaining thermal comfort in indoor environments, particularly for hot and humid climates. Today, air conditioning, comprising cooling and dehumidification, has become a necessity in commercial and residential buildings and industrial processes. It accounts for a major share of the energy consumption of a building or facility. In tropical climates, the energy consumed by heating, ventilation and air-conditioning (HVAC) can exceed 50% of the total energy consumption of a building. This significant figure is primarily due to the heavy duty placed on cooling technologies to remove both sensible and latent heat loads. Therefore, there is tremendous potential to improve the overall efficiency of the air-conditioning systems in buildings. Based on today's practical technology for cooling, the major components of a chiller plant are (I) compressors, (2) cooling towers, (3) pumps (chilled and cooling water) and (4) fans in air handling units. They all consume mainly electricity to operate. When specifying the kW/R ton of a plant, there are two levels of monitoring cooling efficiency: (1) at the efficiency of the chiller machines or the compressors which consume a major amount of electricity; and (2) at the overall efficiency of cooling plants which include the cooling towers, pumps for moving coolant (chilled and cooling water) to all air-handling units. Pragmatically, a holistic approach is necessary towards achieving a low energy input per cooling achieved such as 0.6 kW/R ton cooling or lower by considering all aspects of the cooling plant. In this paper, we present a review of recent innovative cooling technology and strategies that could potentially lower the kW/R ton of cooling systems - from the existing mean of 0.9 kW/R ton towards 0.6 kW/R ton or lower. The paper, broadly divided into three key sections (see Fig. 2), begins with a review of the recent novel devices that enhances the energy efficiency of cooling systems at the component level. This is followed by a review of innovative cooling systems designs that reduces energy use for air conditioning. Lastly, the paper presents recent developments in intelligent air-control strategies and smart chiller sequencing methodologies that reduce the primary energy utilization for cooling. The energy efficient cooling technology, innovative systems designs, and intelligent control strategies described in the paper have been recently researched or are on-going studies. Several have been implemented on a larger scale and, therefore, are examples of practical solutions that can be readily applied to suit specific needs. (C) 2012 Elsevier Ltd. All rights reserved.
引用
收藏
页码:87 / 104
页数:18
相关论文
共 93 条
[1]  
[Anonymous], 2007, PHYS SCI BASIS
[2]  
[Anonymous], PROJ DIR GEN TRANSP
[3]  
APTE MG, 2002, LBNL51570
[4]   Theoretical and experimental investigation on the radial flow desiccant dehumidification bed [J].
Awad, M. M. ;
Ramy K, A. ;
Hamed, A. M. ;
Bekheit, M. M. .
APPLIED THERMAL ENGINEERING, 2008, 28 (01) :75-85
[5]   A multi-phase genetic algorithm for the efficient management of multi-chiller systems [J].
Beghi, Alessandro ;
Cecchinato, Luca ;
Rampazzo, Mirco .
ENERGY CONVERSION AND MANAGEMENT, 2011, 52 (03) :1650-1661
[6]   Performance of vapor compression systems with compressor oil flooding and regeneration [J].
Bell, Ian H. ;
Groll, Eckhard A. ;
Braun, James E. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (01) :225-233
[7]   On the performances of a hybrid air-conditioning system in different climatic conditions [J].
Bergero, Stefano ;
Chiari, Anna .
ENERGY, 2011, 36 (08) :5261-5273
[8]   On-site experimental testing of a novel dew point evaporative cooler [J].
Bruno, Frank .
ENERGY AND BUILDINGS, 2011, 43 (12) :3475-3483
[9]   Comparing different control strategies for indoor thermal comfort aimed at the evaluation of the energy cost of quality of building [J].
Calvino, Francesco ;
La Gennusa, Maria ;
Morale, Massimo ;
Rizzo, Gianfranco ;
Scaccianoce, Gianluca .
APPLIED THERMAL ENGINEERING, 2010, 30 (16) :2386-2395
[10]   Performance evaluation of district cooling plant with ice storage [J].
Chan, Apple L. S. ;
Chow, Tin-Tai ;
Fong, Square K. F. ;
Lin, John Z. .
ENERGY, 2006, 31 (14) :2750-2762