Mechanism Analysis of DFIG-Based Wind Turbinex2019;s Fault Current During LVRT With Equivalent Inductances

被引:41
作者
Chang, Yuanzhu [1 ]
Hu, Jiabing [1 ]
Yuan, Xiaoming [1 ]
机构
[1] Huazhong Univ Sci & Technol, State Key Lab Adv Electromagnet Engn & Technol, Sch Elect & Elect Engn, Wuhan 430074, Peoples R China
基金
中国国家自然科学基金;
关键词
Rotors; Stator windings; Fault currents; Magnetic circuits; Doubly fed induction generators; Couplings; Analytical model; doubly fed induction generator (DFIG); fault currents; low-voltage ride through (LVRT); magnetic circuits; FED INDUCTION GENERATOR; PROTECTION; TURBINES;
D O I
10.1109/JESTPE.2019.2956085
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Doubly fed induction generator (DFIG)-based wind turbine (WT) has a distinct fault current contribution that is critical for the power system analysis. This article analyzes the mechanism underlying DFIG-based WTx2019;s fault current during the low-voltage ride through (LVRT) from the perspective of magnetic circuits. The crowding-out phenomenon is discovered, and the general relationship between flux linkage and current is depicted with the proposed equivalent inductances. Based on the understanding, a new analytical method for deriving the analytical expressions of fault current is proposed. Compared with the existing methods that rely on solving the ordinary differential equations (ODEs), the proposed method is based on the algebraic operation derived from the magnetic circuits, which makes it appropriate for different fault scenarios. Using this method, the stator current is depicted with a series of succinct expressions. The analytical results are verified by experiments and simulations on a 10-kW DFIG prototype. The differences in fault current between the synchronous generator (SG) and DFIG-based WT are identified. This article is expected to help in understanding the regularities of DFIG-based WTx2019;s fault current from a physical perspective. The analytical results are expected to be helpful for rating circuit breakers and studying issues related to protective relays.
引用
收藏
页码:1515 / 1527
页数:13
相关论文
共 40 条
[21]  
[胡家兵 Hu Jiabing], 2019, [中国电机工程学报, Proceedings of the Chinese Society of Electrical Engineering], V39, P5457
[22]   Study of Fault Current Characteristics of the DFIG Considering Dynamic Response of the RSC [J].
Kong, Xiangping ;
Zhang, Zhe ;
Yin, Xianggen ;
Wen, Minghao .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2014, 29 (02) :278-287
[23]  
KU Y.H., 1929, AIEE T, V48, P707
[24]   Dynamic behavior of the doubly fed induction generator during three-phase voltage dips [J].
Lopez, Jesus ;
Sanchis, Pablo ;
Roboam, Xavier ;
Marroyo, Luis .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2007, 22 (03) :709-717
[25]  
Miller Dean., 2015, ANN CONF PROTECT REL, DOI DOI 10.1109/CPRE.2015.7102165
[26]   Ridethrough of wind turbines with doubly-fed induction generator during a voltage dip [J].
Morren, J ;
de Haan, SWH .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2005, 20 (02) :435-441
[27]   Short-circuit current of wind turbines with doubly fed induction generator [J].
Morren, Johan ;
de Haan, Sjoerd W. H. .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2007, 22 (01) :174-180
[28]  
Muljadi E., 2011, 2011 IEEE Power and Energy Society General Meeting, P1
[29]   Impact of Power-Electronic Sources on Transmission Line Ground Fault Protection [J].
Nagpal, Mukesh ;
Henville, Charles .
IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (01) :62-70
[30]   Design of robust intelligent protection technique for large-scale grid-connected wind farm [J].
Noureldeen O. ;