Comparison and analysis on air-to-air and air-to-water heat pump heating systems

被引:30
作者
Xiao, Biao [1 ]
He, Lin [1 ]
Zhang, Shihang [1 ]
Kong, Tingting [1 ]
Hu, Bin [2 ]
Wang, R. Z. [2 ]
机构
[1] GREE Elect Appliances INC, SKL Air Conditioning Equipment & Syst Energy Cons, Zhuhai 519070, Peoples R China
[2] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, 800 Dongchuan Rd, Shanghai 200240, Peoples R China
基金
国家重点研发计划;
关键词
Air-to-air heat pump; Air-to-water heat pump; Operation COP; Air distribution; Thermal comfort; THERMAL COMFORT; SCROLL COMPRESSOR; PERFORMANCE; ROOM;
D O I
10.1016/j.renene.2019.08.033
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
In order to solve the problems of atmospheric pollution and haze caused by traditional coal-fired heating, the promotion and application of clean energy heating methods is urgently needed. The air-source heat pumps are applied in the residential buildings to replace traditional coal-fired heating in Beijing and Tianjin. Limited to the cost and economic conditions, air-source heat pumps are usually installed with the traditional steel radiator. The unreasonable selection and operation of equipment can lead to low energy efficiency of partial load operation. The importance of finding an economical and efficient alternative scheme, therefore, is beyond words. The experimental research and computational fluid dynamics simulation on the performance and air distribution of air-to-air heat pump and air-to-water heat pump under the same operating conditions are done in this paper. The results demonstrate that ATAHP has bigger heating capacity than ATWHP, the decrease of the actual operation COP of ATAHP is 28.30% which is smaller than that of ATWHP by 15.45% with the ambient temperature decreasing from 7 degrees C to -20 degrees C. Thus, ATAHP is better than ATWHP at low temperature operation conditions. The temperature and velocity distribution of indoor air with ATWHP is more uniform, but the high speed air with high temperature with ATAHP blows to the head and feet directly. Consequently, the air distribution with ATAHP is more in line with the requirements of thermal comfort. To conclude, ATAHP has better performance and thermal comfort, and ATAHP is more suitable than ATWHP to be applied and popularized in northern China. (C) 2019 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1888 / 1896
页数:9
相关论文
共 23 条
[1]   TECHNOLOGY REVIEW OF TWO-STAGE VAPOR COMPRESSION HEAT PUMP SYSTEM [J].
Aikins, Kojo Atta ;
Sang-Hyeok, Lee ;
Choi, Jong Min .
INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2013, 21 (03)
[2]   Unsteady thermal performance analysis of a room with serial and parallel duct radiant floor heating system using hot airflow [J].
Bozkir, O ;
Canbazoglu, S .
ENERGY AND BUILDINGS, 2004, 36 (06) :579-586
[3]   A performance comparison between an air-source and a ground-source reversible heat pump [J].
De Swardt, CA ;
Meyer, JP .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2001, 25 (10) :899-910
[4]  
Fan C., 1994, HV AC, V24
[5]   Prediction of thermal comfort, IAQ, and energy consumption in a dense occupancy environment with the under floor air distribution system [J].
Fathollahzadeh, Mohammad Hassan ;
Heidarinejad, Ghassem ;
Pasdarshahri, Hadi .
BUILDING AND ENVIRONMENT, 2015, 90 :96-104
[6]   Can radiant floor heating systems be used in removable glazed enclosed patios meeting thermal comfort standards? [J].
Garcia, Davide Astiaso .
BUILDING AND ENVIRONMENT, 2016, 106 :378-388
[7]   Advanced air source heat pumps for UK and European domestic buildings [J].
Hewitt, Neil J. ;
Huang, Ming Jun ;
Anderson, Mark ;
Quinn, Matthew .
APPLIED THERMAL ENGINEERING, 2011, 31 (17-18) :3713-3719
[8]   Small-scale turbocompressors for wide-range operation with large tip-clearances for a two-stage heat pump concept [J].
Jaued, Adeel ;
Arpagaus, Cordin ;
Bertsch, Stefan ;
Schiffmann, Jurg .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2016, 69 :285-302
[9]   The performance of air-source heat pumps in current and future offices [J].
Jenkins, D. ;
Tucker, R. ;
Ahadzi, M. ;
Rawlings, R. .
ENERGY AND BUILDINGS, 2008, 40 (10) :1901-1910
[10]   A general model for two-stage vapor compression heat pump systems [J].
Jiang, Shuang ;
Wang, Shugang ;
Jin, Xu ;
Zhang, Tengfei .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 51 :88-102